Measurement and Control Basics, 4th Edition
4/5
()
About this ebook
Thomas A. Hughes
Thomas A. Hughes, a Senior Member of ISA, has 30 years of experience in the design and installation of instrumentation and control systems, including 20 years in the management of instrumentation and control projects for the process and nuclear industries. He is the author of two books: Measurement and Control Basics, 4th Edition, (2007) and Programmable Controllers, 4th Edition, (2005), both published by ISA. Mr. Hughes received a B. S. in engineering physics from the University of Colorado, and an M.S. in control systems engineering from Colorado State University. He holds professional engineering licenses in the states of Colorado and Alaska, and has held engineering and management positions with Dow Chemical, Rockwell International, EG&G Rocky Flats, Topro Systems Integration, and the International Atomic Energy Agency. Mr. Hughes has taught numerous courses in electronics, mathematics, and instrumentation systems at the college level and in industry. He lives in Arvada, Colorado.
Related to Measurement and Control Basics, 4th Edition
Related ebooks
Condensed Handbook of Measurement and Control, 3rd Edition Rating: 4 out of 5 stars4/5Fundamentals of Process Control Theory, 3rd Edition Rating: 4 out of 5 stars4/5Advanced Temperature Measurement and Control, Second Edition Rating: 0 out of 5 stars0 ratingsSafety Instrumented Systems Verification – Practical Probabilistic Calculations Rating: 4 out of 5 stars4/5Boiler Control Systems Engineering, Second Edition Rating: 4 out of 5 stars4/5Computer-Controlled Systems: Theory and Design, Third Edition Rating: 3 out of 5 stars3/5Collaborative Process Automation Systems Rating: 5 out of 5 stars5/5Schaum’s Outline of Feedback and Control Systems, 2nd Edition Rating: 4 out of 5 stars4/5Industrial Automation and Control System Security Principles Rating: 4 out of 5 stars4/5Feedback Control Theory Rating: 5 out of 5 stars5/5SCADA: Supervisory Control and Data Acquisition, Fourth Edition Rating: 4 out of 5 stars4/5Guidelines for Engineering Design for Process Safety Rating: 5 out of 5 stars5/5Basic Process Measurements Rating: 0 out of 5 stars0 ratingsAdaptive Control: Second Edition Rating: 4 out of 5 stars4/5Practical Statistical Process Control Rating: 5 out of 5 stars5/5Optimal Control: Linear Quadratic Methods Rating: 4 out of 5 stars4/5Troubleshooting and Root Cause Failure Analysis: Equipment Problem Solving Rating: 5 out of 5 stars5/5Is My Machine OK?: A Field Guide to Assessing Process Machinery Rating: 0 out of 5 stars0 ratingsChemical Reactor Analysis and Applications for the Practicing Engineer Rating: 0 out of 5 stars0 ratingsAdvanced Process Control: Beyond Single Loop Control Rating: 0 out of 5 stars0 ratingsControl Loop Foundation - Batch and Continuous Processes Rating: 4 out of 5 stars4/5Successful Instrumentation and Control Systems Design, Second Edition Rating: 5 out of 5 stars5/5Advanced Control Foundation: Tools, Techniques and Applications Rating: 5 out of 5 stars5/5ISA Handbook of Measurement, Equations and Tables, Second Edition Rating: 5 out of 5 stars5/5Control Valve Primer, Fourth Edition Rating: 3 out of 5 stars3/5Foundation Fieldbus, Fourth Edition Rating: 5 out of 5 stars5/5Automation Made Easy: Everything You Wanted to Know about Automation-and Need to Ask Rating: 4 out of 5 stars4/5Troubleshooting: A Technician's Guide, Second Edition Rating: 4 out of 5 stars4/5Wireless Control Foundation: Continuous and Discrete Control for the Process Industry Rating: 0 out of 5 stars0 ratingsProgrammable Logic Controllers Rating: 4 out of 5 stars4/5
Technology & Engineering For You
The Big Book of Hacks: 264 Amazing DIY Tech Projects Rating: 4 out of 5 stars4/5The Big Book of Maker Skills: Tools & Techniques for Building Great Tech Projects Rating: 4 out of 5 stars4/5The Art of War Rating: 4 out of 5 stars4/5The Art of War Rating: 4 out of 5 stars4/5Nuclear War: A Scenario Rating: 4 out of 5 stars4/5Vanderbilt: The Rise and Fall of an American Dynasty Rating: 4 out of 5 stars4/5Longitude: The True Story of a Lone Genius Who Solved the Greatest Scientific Problem of His Time Rating: 4 out of 5 stars4/5A Night to Remember: The Sinking of the Titanic Rating: 4 out of 5 stars4/5Ultralearning: Master Hard Skills, Outsmart the Competition, and Accelerate Your Career Rating: 4 out of 5 stars4/580/20 Principle: The Secret to Working Less and Making More Rating: 5 out of 5 stars5/5A History of the American People Rating: 4 out of 5 stars4/5The Wuhan Cover-Up: And the Terrifying Bioweapons Arms Race Rating: 4 out of 5 stars4/5The Invisible Rainbow: A History of Electricity and Life Rating: 5 out of 5 stars5/5Navy SEALs Bug-In 2025 Guide: Transform Your Home into an Impenetrable Fortress of Security and Resilience Rating: 0 out of 5 stars0 ratingsRethinking Narcissism: The Bad---and Surprising Good---About Feeling Special Rating: 4 out of 5 stars4/5The Systems Thinker: Essential Thinking Skills For Solving Problems, Managing Chaos, Rating: 4 out of 5 stars4/5The CIA Lockpicking Manual Rating: 5 out of 5 stars5/5Artificial Intelligence: A Guide for Thinking Humans Rating: 4 out of 5 stars4/5The ChatGPT Millionaire Handbook: Make Money Online With the Power of AI Technology Rating: 4 out of 5 stars4/5Death in Mud Lick: A Coal Country Fight against the Drug Companies That Delivered the Opioid Epidemic Rating: 4 out of 5 stars4/5Logic Pro X For Dummies Rating: 0 out of 5 stars0 ratingsSelfie: How We Became So Self-Obsessed and What It's Doing to Us Rating: 4 out of 5 stars4/5The Victorian Internet: The Remarkable Story of the Telegraph and the Nineteenth Century's On-line Pioneers Rating: 4 out of 5 stars4/5Pilot's Handbook of Aeronautical Knowledge (Federal Aviation Administration) Rating: 4 out of 5 stars4/5Broken Money: Why Our Financial System is Failing Us and How We Can Make it Better Rating: 5 out of 5 stars5/5Summary of Nicolas Cole's The Art and Business of Online Writing Rating: 4 out of 5 stars4/5The Homeowner's DIY Guide to Electrical Wiring Rating: 5 out of 5 stars5/5
Related categories
Reviews for Measurement and Control Basics, 4th Edition
11 ratings1 review
- Rating: 2 out of 5 stars2/5simple and easy to understand for non-instrument people,thank you .
Book preview
Measurement and Control Basics, 4th Edition - Thomas A. Hughes
Colorado.
Preface
The fourth edition of Measurement and Control Basics is a thorough and comprehensive treatment of the basic principles of process control and measurement. It is designed for engineers, technicians, management, and sales personnel who are new to process control and measurement. It is also valuable as a concise and easy-to-read reference source on the subject.
This new edition provides expanded coverage of pressure, level, flow, temperature, analytical measurement, and process control computers. Material on the proper tuning of control loops was added to Chapter 1, and expanded coverage of control loops was added to Chapter 2. Chapter 3 includes a more complete discussion of electrical and electronic fundamentals needed in process control and instrumentation.
The discussion of the basic principles underlying pressure measurement has been expanded to include a discussion of sensor characteristics and potentiometric-type pressure sensors. Extensive coverage was added on typical pressure transmitter applications. The discussion on level measurement has been increased with the addition of several common level instruments and switches such as displacers, tape floats, microwave, and radar. The chapter on temperature measurement has been improved by adding new illustrations and a section on radiation pyrometers. Coverage of analytical measurement and control in Chapter 8 was increased by the addition of a section on the principles of electromagnetic radiation and its application to analytical measurement. Three sections were also added to Chapter 8 on photoconductive sensors, photomultiplier tubes, and turbidity analyzers.
Chapter 9 on flow measurement contains new coverage on Reynolds
Number and fluid flow profiles. The discussion of the basic principles of fluid flow has been expanded and improved in Chapter 9. A discussion on types of control valves and control valve actuators was added to Chapter 10 and the section on control valve sizing was expanded and improved.
All of the chapters have been supplemented with new or improved example problems and exercises. Most of the illustrations in the book have been revised and improved.
1
Introduction to Process Control
Introduction
To study the subject of industrial process control effectively, you must first gain a general understanding of its basic principles. To present these control principles clearly and concisely, an intuitive approach to process control is used. First, however, some basic definitions and concepts of process control are presented.
Definition of Process Control
The operations that are associated with process control have always existed in nature. Such natural
process control can be defined as any operation that regulates some internal physical characteristic that is important to a living organism. Examples of natural regulation in humans include body temperature, blood pressure, and heart rate.
Early humans found it necessary to regulate some of their external environmental parameters to maintain life. This regulation could be defined as artificial process control
or more simply as process control,
as we will refer to it in this book. This type of process control is accomplished by observing a parameter, comparing it to some desired value, and initiating a control action to bring the parameter as close as possible to the desired value. One of the first examples of such control was early man’s use of fire to maintain the temperature of his environment.
The term automatic process control came into wide use when people learned to adapt automatic regulatory procedures to manufacture products or pro-cess material more efficiently. Such procedures are called automatic because no human (manual) intervention is required to regulate them.
All process systems consist of three main factors or terms: the manipulated variables, disturbances, and the controlled variables (Figure 1-1). Typical manipulated variables are valve position, motor speed, damper position, or blade pitch. The controlled variables are those conditions— such as temperature, level, position, pressure, pH, density, moisture content, weight, and speed—that must be maintained at some desired value. For each controlled variable there is an associated manipulated variable. The control system must adjust the manipulated variables so the desired value or set point
of the controlled variable is maintained despite any disturbances.
Figure 1-1. Process control variables
Disturbances enter or affect the process and tend to drive the controlled variables away from their desired value or set point condition. Typical disturbances include changes in ambient temperature, in demand for product, or in the supply of feed material. The control system must adjust the manipulated variable so the set point value of the controlled variable is maintained despite the disturbances. If the set point is changed, the manipulated quantity must be changed to adjust the controlled variable to its new desired value.
For each controlled variable the control system operator selects a manipulated variable that can be paired with the controlled variable. Often the choice is obvious, such as manipulating the flow of fuel to a home furnace to control the temperature of the house. Sometimes the choice is not so obvious and can only be determined by someone who understands the process under control. The pairing of manipulated and controlled variables is performed as part of the process design.
Elements of a Process Control System
Figure 1-2 illustrates the essential elements of a process control system. In the system shown, a level transmitter (LT), a level controller (LC), and a control valve (LV) are used to control the liquid level in a process tank. The purpose of this control system is to maintain the liquid level at some prescribed height (H) above the bottom of the tank. It is assumed that the rate of flow into the tank is random. The level transmitter is a device that measures the fluid level in the tank and converts it into a useful measurement signal, which is sent to a level controller. The level controller evaluates the measurement, compares it with a desired set point (SP), and produces a series of corrective actions that are sent to the control valve. The valve controls the flow of fluid in the outlet pipe to maintain a level in the tank.
Figure 1-2. Process level control: Example
Thus, a process control system consists of four essential elements: process, measurement, evaluation, and control. A block diagram of these elements is shown in Figure 1-3. The diagram also shows the disturbances that enter or affect the process. If there were no upsets to a process, there would be no need for the control system. Figure 1-3 also shows the input and output of the process and the set point used for control.
Figure 1-3. Four elements of a control system
Process
In general, a process consists of an assembly of equipment and material that is related to some manufacturing operation or sequence. In the example presented in Figure 1-2, the process whose liquid level is placed under control includes such components as a tank, the liquid in the tank, the flow of liquid into and out of the tank, and the inlet and outlet piping. Any given process can involve many dynamic variables, and it may be desirable to control all of them. In most cases, however, controlling only one variable will be sufficient to control the process to within acceptable limits. One occasionally encounters a multivariable process in which many variables, some interrelated, require regulation.
Measurement
To control a dynamic variable in a process, you must have information about the entity or variable itself. This information is obtained by measuring the variable.
Measurement refers to the conversion of the process variable into an analog or digital signal that can be used by the control system. The device that performs the initial measurement is called a sensor or instrument. Typical measurements are pressure, level, temperature, flow, position, and speed. The result of any measurement is the conversion of a dynamic variable into some proportional information that is required by the other elements in the process control loop or sequence.
Evaluation
In the evaluation step of the process control sequence, the measurement value is examined, compared with the desired value or set point, and the amount of corrective action needed to maintain proper control is deter- mined. A device called a controller performs this evaluation. The controller can be a pneumatic, electronic, or mechanical device mounted in a control panel or on the process equipment. It can also be part of a computer control system, in which case the control function is performed by software.
Control
The control element in a control loop is the device that exerts a direct influence on the process or manufacturing sequence. This final control element accepts an input from the controller and transforms it into some proportional operation that is performed on the process. In most cases, this final control element will be a control valve that adjusts the flow of fluid in a process. Devices such as electrical motors, pumps, and dampers are also used as control elements.
Process and Instrumentation Drawings
In the measurement and control field, a standard set of symbols is used to prepare drawings of control systems and processes. The symbols used in these drawings are based on the standard ISA-5.1-1984 (R1992) Instrumentation Symbols and Identification, which was developed by ISA. A typical application for this standard is process and instrumentation diagrams (P&IDs), which show the interconnection of the process equipment and the instrumentation used to control the process. A portion of a typical P&ID is shown in Figure 1-4.
In standard P&IDs, the process flow lines, such as process fluid and steam, are indicated with heavier solid lines than the lines that are used to represent the instrument. The instrument signal lines use special markings to indicate whether the signal is pneumatic, electric, hydraulic, and so on. Table A-1 in Appendix A lists the instrument line symbols that are used on P&IDs and other instrumentation and control drawings. In Figure 1-4, two types of instrument signals are used: double cross-hatched lines denote the pneumatic signals to the steam control valve and the process outlet flow control valve, and a dashed line is used for the electrical control lines between various instruments. In process control applications, pneumatic signals are almost always 3 to 15 psi (i.e., pounds per square inch, gauge pressure), and the electric signals are normally 4 to 20 mA (milliamperes) DC (direct current).
A balloon symbol with an enclosed letter and number code is used to represent the instrumentation associated with the process control loop. This letter and number combination is called an instrument identification or instrument tag number.
Figure 1-4. P&ID: Example
The first letter of the tag number is normally chosen so that it indicates the measured variable of the control loop. In the sample P&ID shown in Figure 1-4, T is the first letter in the tag number that is used for the instruments in the temperature control loop. The succeeding letters are used to represent a readout or passive function or an output function, or the letter can be used as a modifier. For example, the balloon in Figure 1-4 marked TE represents a temperature element and that marked TIC is a temperature-indicating controller. The line across the center of the TIC balloon symbol indicates that the controller is mounted on the front of a main control panel. No line indicates a field-mounted instrument, and two lines mean that the instrument is mounted in a local or field-mounted panel. Dashed lines indicate that the instrument is mounted inside the panel.
Normally, sequences of three- or four-digit numbers are used to identify each loop. In our process example (Figure 1-4), we used loop numbers 100 and 101. Smaller processes use three-digit loop numbers; larger processes or complex manufacturing plants may require four or more digits to identify all the control loops.
Special marks or graphics are used to represent process equipment and instruments. For example, in our P&ID example in Figure 1-4, two parallel lines represent the orifice plate that is used to detect the discharge flow from the process heater. The two control valves in the figure also use a special symbol. See Appendix A for a more detailed discussion of the instrumentation and process symbols that are used on P&IDs.
General Requirements of a Control System
The primary requirement of a control system is that it be reasonably stable. In other words, its speed of response must be fairly fast, and this response must show reasonable damping. A control system must also be able to reduce the system error to zero or to a value near zero.
System Error
The system error is the difference between the value of the controlled variable set point and the value of the process variable maintained by the system. The system error is expressed in equation form by the following:
where
System Response
The main purpose of a control loop is to maintain some dynamic process variable (pressure, flow, temperature, level, etc.) at a prescribed operating point or set point. System response is the ability of a control loop to recover from a disturbance that causes a change in the controlled process variable.
There are two general types of good response: underdamped (cyclic response) and damped. Figure 1-5 shows an underdamped or cyclic response of a system in which the process variable oscillates around the set point after a process disturbance. The wavy response line shown in the figure represents an acceptable response if the process disturbance or change in set point is large, but it will not be an acceptable response if the change from the set point is small.
Figure 1-6 shows a damped response where the control system is able to bring the process variable back to the operating point with no oscillations.
Figure 1-5. Cyclic response to process disturbance
Figure 1-6. Damped response to process disturbance
Control Loop Design Criteria
Many criteria are employed to evaluate the process control’s loop response to an input change. The most common of these include settling time, maximum error, offset error, and error area (Figure 1-7).
Figure 1-7. Evaluation of control loop response
When there is a process disturbance or a change in set point, the settling time is defined as the time the process control loop needs to bring the process variable back to within an allowable error. The maximum error is simply the maximum allowable deviation of the dynamic variable. Most control loops have certain inherent linear and nonlinear qualities that prevent the system from returning the process variable to the set point after a system change. This condition is generally called offset error and will be discussed later in this chapter. The error area is defined as the area between the response curve and the set point line as shown by the shaded area in Figure 1-7.
These four evaluation criteria are general measures of control loop behavior that are used to determine the adequacy of the loop’s ability to perform some desired function. However, perhaps the best way to gain a clear understanding of process control is to take an intuitive approach.
Intuitive Approach to Process Control Concepts
The practice of process control arose long before the theory or analytical methods underlying it were developed. Processes and controllers were designed using empirical methods that were based on intuition (feel
) and extensive process experience. Most of the reasoning involved was nonmathematical. This approach was unscientific trial and error, but it was a successful control method.
Consider, for example, an operator looking into an early metal processing furnace to determine whether the product was finished. He or she used flame color, amount of smoke, and process time to make this judgment. From equally direct early methods evolved most of the control concepts and hardware used today. Only later did theories and mathematical techniques emerge to explain how and why the systems responded as they did.
In this section, we will approach the study of control fundamentals in much the same way that control knowledge developed—that is, through a step-by-step procedure starting from manual control and moving to ever- increasing automatic control.
Suppose we have a process like that shown in Figure 1-8. A source of feed liquid flows into a tank at a varying rate from somewhere else in a process plant. This liquid must be heated so that it emerges at a desired temperature, Td, as a hot liquid. To accomplish this, hot water, which is available from another part of the plant, flows through heat exchanger coils in the tank. By controlling the flow of hot water, we can obtain the desired temperature, Td. A further process requirement is that the level of the tank must neither overflow nor fall so low that it exposes the heater coils.
Figure 1-8. Example process – using manual valves
The temperature is measured in the tank, and a temperature transmitter (TT-1) converts the signal into a 4-20 mA direct current (DC) signal to drive a temperature indicator (TI-1) mounted near the hot water inlet valve. Similarly, a level indicator (LI-2) is mounted within the operator's view of the hot feed outlet valve (HV-2).
Suppose a process operator has the task of holding the temperature, T, near the desired temperature, Td, while making sure the tank doesn't overflow or the level get too low. The question is how the operator would cope with this task over a period of time. He or she would manually adjust the hot water inlet valve (HV-1) to maintain the temperature and occasionally adjust the outlet valve (HV-2) to maintain the correct level in the tank.
The operator would face several problems, however. Both indicators would have to be within the operator's view, and the manual valves would have to be close to the operator and easy to adjust.
On/Off Control
To make the operator’s work easier, suppose we install electrically operated solenoid valves in place of the manual valves, as shown in Figure 1-9. We can also install two hand switches (HS-1 and HS-2) so the solenoid valves can be operated from a common location. The valves can assume two states, either fully open (on) or fully closed (off). This type of control is called two-position or on/off control.
Figure 1-9. Sample process: Solenoid valves
Assume for the moment that the level is holding steady and that the main concern is controlling temperature. The operator has been told to keep the temperature of the fluid in the tank at 100°F. He or she compares the reading of the temperature indicator with the selected set point of 100°F. The operator closes the hot water valve when the temperature of the fluid in the tank rises above the set point (Figure 1-10). Because of process dead time and lags the temperature will continue to rise before reversing and moving toward the set point. When the temperature falls below 100°F, the operator opens the hot water valve. Again, dead time and lags in the process create a delay before the temperature begins to rise. As it crosses the set point, the operator again shuts off the hot water, and the cycle repeats.
This cycling is normal for a control system that uses on/off control. This limitation exists because it’s impossible for the operator to control the process exactly with only two options.
This on/off type of control can be expressed mathematically as follows:
Figure 1-10. ON/OFF temperature control
where
In the on/off control mode, the valve is opened when the error (e) is positive (+), and the valve is closed when e is negative (–).
Proportional Control
When we view the process as a balance between energy in and energy out, it is clear that smoother control would result if a steady flow of hot water were maintained rather than the sudden changes between ON and OFF. The problem is finding the correct value for the steady flow required for proper control. Obviously, for each rate of feed flow in and out of the tank, some ideal amount of inlet water flow exists that will hold the outlet temperature, T, at 100°F.
This suggests that we should make two modifications to our control mode or strategy. The first is to establish some steady-flow value for the hot water that, at average operating conditions, tends to hold the process variable (temperature) at the desired value or set point (100°F). Once that average flow value has been established for the hot water, increases or decreases of error (e = SP – PV) must be allowed to cause corresponding increases and decreases in water flow from this normal value. This illustrates the concept of proportional control (i.e., initiating a corrective action to a value that is in some proportion to the change in error or deviation of the process variable from set point).
Before proportional control can be implemented on our sample process, we must change the solenoid valves to adjustable control valves. Such valves can be positioned to any degree of opening—from fully closed to fully opened—depending on the type of valve actuator mechanism you choose (generally either an electrically or pneumatically operated diaphragm actuator). Our sample process now looks like Figure 1-11, which now shows the use of pneumatically operated control valves (TV-1 and LV-2) and process controllers (TIC-1 and LIC-2). Control valves and controllers in the system make it possible to achieve better control of the process.
Figure 1-11. Sample process: Proportional control
Proportional control can be described mathematically as follows:
where
Proportional control can be illustrated by using the three graphs in Figure 1-12 and setting the proportional constant to three different values (i.e., Kc = 1, Kc <1, and Kc >1).
Figure 1-12. Proportional control
As these graphs show, the amount of valve change (ΔV) for a given error can vary substantially. A one-to-one relationship is shown in Figure 1-12(a). In that example, the control valve would move 1 percent of its full travel for a corresponding 1 percent change in error or in a one-to-one ratio. In Figure 1-12(b), where a low gain (Kc <1) is selected, a large change in error is required before the control valve would be fully opened or closed. Finally, Figure 1-12(c) shows the case of high gain (Kc >1), where a very small error would cause a large change in the control valve position.
The term proportional gain, or simply gain, arose as a result of the use of analytical methods in process control. Historically, the proportionality between error and valve action was called proportional band (PB). Proportional band is the expression that states the percentage of change in error that is required to move the valve full scale. Again, this had intuitive plausibility because it gave an operator a feel for how small of an error caused full corrective action. Thus, a 10 percent proportional band meant that a 10 percent error between SP and PV would cause the output to go full scale.
This definition can be related to proportional gain Kc by noting the following equation:
An example will help you understand the relationship between proportional band and gain.
EXAMPLE 1-1
Problem: For a proportional process controller:
What proportional band corresponds to a gain of 0.4?
What gain corresponds to a PB of 400?
The modern way of considering proportional control is to think in terms of gain (Kc). The m term, as Equation 1-3 shows, has to be that control valve position that supplies just the right amount of hot water to make the temperature 100°F, that is, PV = SP. The position, m, indicated in Figures 1-12(a), (b), and (c), is often called the manual (m) reset because it is a manual controller adjustment.
When a controller is designed to provide this mode of control, it must contain at least two adjustments: one for the Kc term and one for the m term. Control has become more complicated because it is now necessary to know where to set Kc and m for best control.
It would not take too long for the operator of our sample process to discover a serious problem with proportional control. Proportional control rarely ever keeps the process variable at the set point if there are frequent disturbances to the process. For example, suppose the flow to the tank suddenly increases. If the temperature of the tank is to be maintained at 100°F at this new rate of feed flow, more hot water must be supplied. This calls for a change in valve position. According to Equation 1-3, the only way that the valve position (V) can be changed is for the error (e) to change. Remember that m is a constant. Thus, an error will occur, and the temperature will drop below 100°F until an equilibrium is reached between the hot water flow and new feed flow. How much this drop will be depends on the value of Kc that was set in the controller as well as on the characteristics of the process. The larger Kc is, the smaller this offset will be in a given system.
However, it can be shown that Kc cannot be increased indefinitely because the control loop will become unstable. So, some error is inevitable if the feed rate changes. These points are illustrated in Figure 1-13, which shows a plot of hot feed temperature versus hot water flow rate (valve position) for both low raw feed flow and high raw feed flow.
For the hot water valve in position 1 and the raw feed coming into the process tank at the low flow rate, the process would heat the fluid and produce hot feed fluid at temperature T2. If suddenly the feed went to the high flow rate and the valve position was not changed, the temperature would drop to T1. At this new high flow rate, the hot water valve must be moved to position 2 if the original temperature T2 is to be restored. Figure 1-14 shows the extent to which proportional control of the temperature valve can achieve this restoration.
One way to cope with the offset problem is by manually adjusting the m term. When we adjust the m term (usually through a knob on a process controller), we are moving the valve to a new position that allows PV to equal SP under the new conditions of load. In this case, with an increase in feed flow, Equation 1-3 clearly shows that the only way to obtain a new value for V, if e is to be zero, is by changing the m term. If process changes are frequent or large it may become necessary to adjust m frequently. It is apparent that some different type of control mode is needed.